Electrical & explosive atmospheres

EN 60079-1

Explosive atmospheres: flameproof enclosures "d"

The type of protection that contains an explosion inside the enclosure and stops it propagating out.

A flameproof enclosure (Ex d) works on a different logic from the other methods: it does not prevent ignition. It accepts that an explosion will occur inside the enclosure and ensures that it stays there.

How it works

  • The enclosure is strong enough to withstand the pressure of an internal explosion without deforming.
  • Every joint — lid, shaft, cable entry — is machined to a precisely specified gap and flame path length.
  • Hot gases passing through that gap are cooled enough that they can no longer ignite the atmosphere outside.

Practical consequences for maintenance

This is the detail most often overlooked: the flame path gap on a flameproof enclosure is specified to hundredths of a millimetre. Opening and closing must be done correctly, with every bolt torqued to specification. A scratch, corrosion or paint on the flame path surface voids the protection. Flame paths are cleaned only with non-abrasive means and, where needed, a non-setting corrosion inhibitor.

Ex d equipment is typically used for motors, control boxes, luminaires and switchgear, where eliminating sparking altogether is not feasible.